# ASHRAE Guideline 36-2021 4.1 4.1 VAV Terminal Unit—Cooling Only

This component model is an example of the variable air volume (VAV) terminal unit cooling only from Guideline 36-2021 Section 4.1, illustrated in Figure A-1.
This component model is an example of the variable air volume (VAV) terminal unit with cooling only from Guideline 36-2021 Section 4.1, illustrated in Figure A-1.

![](../_static/images/g36-4.1.png)

Expand Down
2 changes: 1 addition & 1 deletion examples/guideline36-2021-4.1.html
Original file line number Diff line number Diff line change
Expand Up @@ -381,7 +381,7 @@ <h2> Contents </h2>

<section class="tex2jax_ignore mathjax_ignore" id="ashrae-guideline-36-2021-4-1-4-1-vav-terminal-unitcooling-only">
<h1>ASHRAE Guideline 36-2021 4.1 4.1 VAV Terminal Unit—Cooling Only<a class="headerlink" href="#ashrae-guideline-36-2021-4-1-4-1-vav-terminal-unitcooling-only" title="Permalink to this heading">#</a></h1>
<p>This component model is an example of the variable air volume (VAV) terminal unit cooling only from Guideline 36-2021 Section 4.1, illustrated in Figure A-1.</p>
<p>This component model is an example of the variable air volume (VAV) terminal unit with cooling only from Guideline 36-2021 Section 4.1, illustrated in Figure A-1.</p>
<p><img alt="" src="../_images/g36-4.1.png" /></p>
<section id="downloads">
<h2>Downloads<a class="headerlink" href="#downloads" title="Permalink to this heading">#</a></h2>
Expand Down
194 changes: 97 additions & 97 deletions guideline36-2021-4-1.jsonld
Original file line number Diff line number Diff line change
@@ -1,19 +1,51 @@
[
{
"@id": "urn:ex/in-connection",
"@id": "urn:ex/discharge-air-flow",
"@type": [
"http://data.ashrae.org/standard223#Connection"
"http://data.ashrae.org/standard223#QuantifiableObservableProperty"
],
"http://data.ashrae.org/standard223#hasMedium": [
"http://data.ashrae.org/standard223#hasAspect": [
{
"@id": "http://data.ashrae.org/standard223#Medium-Air"
"@id": "http://data.ashrae.org/standard223#Role-Discharge"
}
],
"http://qudt.org/schema/qudt/hasQuantityKind": [
{
"@id": "http://qudt.org/vocab/quantitykind/VolumeFlowRate"
}
],
"http://qudt.org/schema/qudt/hasUnit": [
{
"@id": "http://qudt.org/vocab/unit/FT3-PER-MIN"
}
]
},
{
"@id": "urn:ex/",
"@id": "urn:ex/discharge-air-flow-sensor",
"@type": [
"http://www.w3.org/2002/07/owl#Ontology"
"http://data.ashrae.org/standard223#Sensor"
],
"http://data.ashrae.org/standard223#hasObservationLocation": [
{
"@id": "urn:ex/out"
}
],
"http://data.ashrae.org/standard223#observes": [
{
"@id": "urn:ex/discharge-air-flow"
}
]
},
{
"@id": "urn:ex/duct-before-damper",
"@type": [
"http://data.ashrae.org/standard223#Connection",
"http://data.ashrae.org/standard223#Duct"
],
"http://data.ashrae.org/standard223#hasMedium": [
{
"@id": "http://data.ashrae.org/standard223#Medium-Air"
}
]
},
{
Expand All @@ -33,72 +65,66 @@
]
},
{
"@id": "urn:ex/discharge-air-flow",
"@id": "urn:ex/out-connection",
"@type": [
"http://data.ashrae.org/standard223#QuantifiableObservableProperty"
"http://data.ashrae.org/standard223#Connection"
],
"http://data.ashrae.org/standard223#hasMedium": [
{
"@id": "http://data.ashrae.org/standard223#Medium-Air"
}
]
},
{
"@id": "urn:ex/damper-command",
"@type": [
"http://data.ashrae.org/standard223#QuantifiableActuatableProperty"
],
"http://data.ashrae.org/standard223#hasAspect": [
{
"@id": "http://data.ashrae.org/standard223#Role-Discharge"
"@id": "http://data.ashrae.org/standard223#EnumerationKind-Position"
}
],
"http://qudt.org/schema/qudt/hasQuantityKind": [
{
"@id": "http://qudt.org/vocab/quantitykind/VolumeFlowRate"
"@id": "http://qudt.org/vocab/quantitykind/DimensionlessRatio"
}
],
"http://qudt.org/schema/qudt/hasUnit": [
{
"@id": "http://qudt.org/vocab/unit/FT3-PER-MIN"
"@id": "http://qudt.org/vocab/unit/PERCENT"
}
]
},
{
"@id": "urn:ex/damper-in",
"@id": "urn:ex/in-connection",
"@type": [
"http://data.ashrae.org/standard223#InletConnectionPoint"
],
"http://data.ashrae.org/standard223#cnx": [
{
"@id": "urn:ex/duct-before-damper"
}
"http://data.ashrae.org/standard223#Connection"
],
"http://data.ashrae.org/standard223#hasMedium": [
{
"@id": "http://data.ashrae.org/standard223#Medium-Air"
}
],
"http://data.ashrae.org/standard223#mapsTo": [
{
"@id": "urn:ex/in"
}
]
},
{
"@id": "urn:ex/damper-actuator",
"@id": "urn:ex/damper-in",
"@type": [
"http://data.ashrae.org/standard223#Actuator"
"http://data.ashrae.org/standard223#InletConnectionPoint"
],
"http://data.ashrae.org/standard223#actuates": [
"http://data.ashrae.org/standard223#cnx": [
{
"@id": "urn:ex/damper"
"@id": "urn:ex/duct-before-damper"
}
],
"http://data.ashrae.org/standard223#commandedByProperty": [
"http://data.ashrae.org/standard223#hasMedium": [
{
"@id": "urn:ex/damper-command"
"@id": "http://data.ashrae.org/standard223#Medium-Air"
}
]
},
{
"@id": "urn:ex/duct-before-damper",
"@type": [
"http://data.ashrae.org/standard223#Connection",
"http://data.ashrae.org/standard223#Duct"
],
"http://data.ashrae.org/standard223#hasMedium": [
"http://data.ashrae.org/standard223#mapsTo": [
{
"@id": "http://data.ashrae.org/standard223#Medium-Air"
"@id": "urn:ex/in"
}
]
},
Expand Down Expand Up @@ -126,35 +152,9 @@
]
},
{
"@id": "urn:ex/out",
"@type": [
"http://data.ashrae.org/standard223#OutletConnectionPoint"
],
"http://data.ashrae.org/standard223#cnx": [
{
"@id": "urn:ex/out-connection"
}
],
"http://data.ashrae.org/standard223#hasMedium": [
{
"@id": "http://data.ashrae.org/standard223#Medium-Air"
}
],
"http://data.ashrae.org/standard223#hasProperty": [
{
"@id": "urn:ex/discharge-air-flow"
}
]
},
{
"@id": "urn:ex/out-connection",
"@id": "urn:ex/",
"@type": [
"http://data.ashrae.org/standard223#Connection"
],
"http://data.ashrae.org/standard223#hasMedium": [
{
"@id": "http://data.ashrae.org/standard223#Medium-Air"
}
"http://www.w3.org/2002/07/owl#Ontology"
]
},
{
Expand All @@ -178,23 +178,18 @@
]
},
{
"@id": "urn:ex/damper-out",
"@id": "urn:ex/damper-position",
"@type": [
"http://data.ashrae.org/standard223#OutletConnectionPoint"
],
"http://data.ashrae.org/standard223#cnx": [
{
"@id": "urn:ex/duct-after-damper"
}
"http://data.ashrae.org/standard223#QuantifiableObservableProperty"
],
"http://data.ashrae.org/standard223#hasMedium": [
"http://qudt.org/schema/qudt/hasQuantityKind": [
{
"@id": "http://data.ashrae.org/standard223#Medium-Air"
"@id": "http://qudt.org/vocab/quantitykind/DimensionlessRatio"
}
],
"http://data.ashrae.org/standard223#mapsTo": [
"http://qudt.org/schema/qudt/hasUnit": [
{
"@id": "urn:ex/out"
"@id": "http://qudt.org/vocab/unit/PERCENT"
}
]
},
Expand All @@ -211,55 +206,60 @@
]
},
{
"@id": "urn:ex/damper-position",
"@id": "urn:ex/damper-actuator",
"@type": [
"http://data.ashrae.org/standard223#QuantifiableObservableProperty"
"http://data.ashrae.org/standard223#Actuator"
],
"http://qudt.org/schema/qudt/hasQuantityKind": [
"http://data.ashrae.org/standard223#actuates": [
{
"@id": "http://qudt.org/vocab/quantitykind/DimensionlessRatio"
"@id": "urn:ex/damper"
}
],
"http://qudt.org/schema/qudt/hasUnit": [
"http://data.ashrae.org/standard223#commandedByProperty": [
{
"@id": "http://qudt.org/vocab/unit/PERCENT"
"@id": "urn:ex/damper-command"
}
]
},
{
"@id": "urn:ex/discharge-air-flow-sensor",
"@id": "urn:ex/damper-out",
"@type": [
"http://data.ashrae.org/standard223#Sensor"
"http://data.ashrae.org/standard223#OutletConnectionPoint"
],
"http://data.ashrae.org/standard223#hasObservationLocation": [
"http://data.ashrae.org/standard223#cnx": [
{
"@id": "urn:ex/out"
"@id": "urn:ex/duct-after-damper"
}
],
"http://data.ashrae.org/standard223#observes": [
"http://data.ashrae.org/standard223#hasMedium": [
{
"@id": "urn:ex/discharge-air-flow"
"@id": "http://data.ashrae.org/standard223#Medium-Air"
}
],
"http://data.ashrae.org/standard223#mapsTo": [
{
"@id": "urn:ex/out"
}
]
},
{
"@id": "urn:ex/damper-command",
"@id": "urn:ex/out",
"@type": [
"http://data.ashrae.org/standard223#QuantifiableActuatableProperty"
"http://data.ashrae.org/standard223#OutletConnectionPoint"
],
"http://data.ashrae.org/standard223#hasAspect": [
"http://data.ashrae.org/standard223#cnx": [
{
"@id": "http://data.ashrae.org/standard223#EnumerationKind-Position"
"@id": "urn:ex/out-connection"
}
],
"http://qudt.org/schema/qudt/hasQuantityKind": [
"http://data.ashrae.org/standard223#hasMedium": [
{
"@id": "http://qudt.org/vocab/quantitykind/DimensionlessRatio"
"@id": "http://data.ashrae.org/standard223#Medium-Air"
}
],
"http://qudt.org/schema/qudt/hasUnit": [
"http://data.ashrae.org/standard223#hasProperty": [
{
"@id": "http://qudt.org/vocab/unit/PERCENT"
"@id": "urn:ex/discharge-air-flow"
}
]
}
Expand Down