Fix VRF FluidTCtrl negative outdoor unit fan power #10649
base: develop
Are you sure you want to change the base?
Conversation
as QCoil is negative in cooling mode, directly using m_air = Q_coil / (T_coil_out - T_coil_in) / 1005.0 will result in negative air flow, as well as downstream fan power Here QCoil should be abs(QCoil)
@@ -13288,7 +13288,7 @@ Real64 VRFCondenserEquipment::VRFOU_FlowRate(EnergyPlusData &state, | |||
deltaT = this->C3Tc * pow_2(SHSC) + this->C2Tc * SHSC + this->C1Tc; | |||
T_coil_surf = TeTc - deltaT; | |||
T_coil_out = T_coil_in + (T_coil_surf - T_coil_in) * (1 - BF); | |||
m_air = Q_coil / (T_coil_out - T_coil_in) / 1005.0; | |||
m_air = abs(Q_coil) / (T_coil_out - T_coil_in) / 1005.0; |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
If I'm understanding Q_coil
correctly, it should never be <0. While this fixes the issue (which occurs only a few timesteps in the year) it masks a problem higher up. The Q that is passed in to this function shouldn't be <0, ever.
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
So Q_coil is negative when it's in cooling mode. It is positive when it's heating
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
So Q_coil is negative when it's in cooling mode. It is positive when it's heating
I'm not sure that's the case. Q_coil
here is the heat rejection when the unit is in cooling mode. So it's heating the outdoor air, so (Tcoilout-Tcoilin) should be positive, so you would expect Q_coil
to be positive.
In the next block where it's in heating mode (so it's cooling the outdoor air) delta is (h_coil_in - h_coil_out
so, again deltaH is positive and so Q_coil
should be positive.
I ran in the debugger and saw both positive and negative values of Q_coil
in the OperationMode == HXOpMode::CondMode
block. Tried to watch the values in the OperationMode == HXOpMode::EvapMode
block, but it never goes there. Even with Atlanta weather. That doesn't seem correct. Is it possible that the value passed in for OperationMode
is not correct here?
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Now I'm not certain whether Q_coil
should be always positive or not.
Although, from the definition of this function, it seems they do need to be absolute value of Q_coil
.
Real64 VRFCondenserEquipment::VRFOU_FlowRate(EnergyPlusData &state,
HXOpMode const OperationMode, // Mode 0 for running as condenser, 1 for evaporator
Real64 const TeTc, // VRF Tc at cooling mode, or Te at heating mode [C]
Real64 const SHSC, // SC for OU condenser or SH for OU evaporator [C]
Real64 const Q_coil, // absolute value of OU coil heat release or heat extract [W] <----- here they require absolute value
Real64 const T_coil_in, // Temperature of air at OU coil inlet [C]
Real64 const W_coil_in // Humidity ratio of air at OU coil inlet [kg/kg]
) const
{
Maybe I should just add a Q_coil = abs(Q_coil)
at the beginning of the call to this function? @mjwitte
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Maybe I should just add a Q_coil = abs(Q_coil) at the beginning of the call to this function?
No, I think that will mask other problems. To me, the "absolute value" comment implies that the value passed in will always be positive. We need to understand if HXOpMode
is being passed in correctly and better understand the variables that are being passed in for Q_coil
.
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
I see. I will look into it. Currently there are definitely both positive and negatives for the same mode
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
I've done some investigations and had a few findings. Although I'm not sure if this is enough to figure out a fix. @mjwitte
about the operation mode
According to the documentation, there are 6 heat recovery modes
- Mode 1: Cooling load only. No heating load. Both OU heat exchangers operate as condensers.
- Mode 2: Simultaneous heating and cooling. The sum of the zone cooling loads and compressor heat is much larger than the sum of the zone heating loads. Both OU heat exchangers operate as condensers.
- Mode 3: Simultaneous heating and cooling. The sum of the zone cooling loads and compressor heat is slightly larger than the sum of the zone heating loads. One OU heat exchanger operates as a condenser while the other as an evaporator.
- Mode 4: Simultaneous heating and cooling. The sum of the zone cooling loads and compressor heat is slightly smaller than the sum of the zone heating loads. One OU heat exchanger operates as a condenser while the other as an evaporator.
- Mode 5: Simultaneous heating and cooling. The sum of the zone cooling loads and compressor heat is much smaller than the sum of the zone heating loads. Both OU heat exchangers operate as evaporators.
- Mode 6: Heating load only. No cooling load. Both OU heat exchangers operate as evaporators.
Here is how the heat recovery mode is determined
// Determine FlagToLower
// this->DiffOUTeTo is "Difference between Outdoor Unit Evaporating Temperature and Outdoor Air Temperature in Heat Recovery Mode" from user input
if (state.dataEnvrn->OutDryBulbTemp - this->DiffOUTeTo < Tsuction) {
temp_Tsuction = state.dataEnvrn->OutDryBulbTemp - this->DiffOUTeTo;
FlagToLower = true;
} else {
temp_Tsuction = Tsuction;
FlagToLower = false;
}
// Calculate compressor speed satisfying IU loads: rps1_evap & rps2_cond
this->VRFOU_CompSpd(state, Q_c_TU_PL, HXOpMode::EvapMode, temp_Tsuction, Tdischarge, h_IU_evap_in, h_IU_PLc_out, rps1_evap);
this->VRFOU_CompSpd(state, Q_h_TU_PL, HXOpMode::CondMode, temp_Tsuction, Tdischarge, h_IU_evap_in, h_IU_PLc_out, rps2_cond);
// Determine FlagMode5
if (rps1_evap <= rps2_cond) {
FlagMode5 = true;
} else {
FlagMode5 = false;
}
// Determine HR Mode
if (FlagMode5) {
HRMode = 5;
if (FlagToLower)
HRMode_sub = 1;
else
HRMode_sub = 2;
} else {
if (FlagToLower)
HRMode = 3; // Mode 3&4 share the same logics below
else
HRMode = 2;
}
One issue I saw is that rps2_cond
is negative sometimes. Here's some debugging print. I used the
VariableRefrigerantFlow_FluidTCtrl_HR_5Zone.idf
and USA_FL_Miami.Intl.AP.722020_TMY3.epw
combination. For the 01/02 07, 4th time step, rps2_cond
is negative.
01/02 07-4 HRMode=2, flag5=false, rps1_evap=14.796895201613392,rps2_cond=-103.04599155624868: Q_c_TU_PL=279.7809733457191, Q_h_TU_PL=300.59323456715885, temp_Tsuction=14.000000000000002,Tdischarge=36
This is caused by the following in VRFCondenserEquipment::VRFOU_CompSpd
, where Q_req
is smaller than the CompEvaporatingPWRSpd(CounterCompSpdTemp)
when CounterCompSpdTemp = 1
.
Q_cond_req = Q_req;
...
Q_evap_req = Q_cond_req - CompEvaporatingPWRSpd(CounterCompSpdTemp);
I was considering, maybe Q_evap_req = Q_cond_req - CompEvaporatingPWRSpd(CounterCompSpdTemp);
should be Q_evap_req = max(0.0, Q_cond_req - CompEvaporatingPWRSpd(CounterCompSpdTemp));
Even with this, there still remains a question of how this "much larger" or "much smaller" in mode 2 and 5 is reflected in the code. I feel the current code seems to be just testing for "larger" or "smaller".
about the Q_coil
sign
the input argument Q_h_OU
in m_air_cond = this->VRFOU_FlowRate( state, HXOpMode::CondMode, Tdischarge, this->SC, Q_h_OU, state.dataEnvrn->OutDryBulbTemp, state.dataEnvrn->OutHumRat);
corresponds to the Q_coil
referred to in the last comment.
Here is how it's computed. As Q_c_tot + Ncomp
is smaller than Q_h_TU_PL
, the Q_h_OU
is negative.
// compressor: Ncomp & Q_c_tot
this->VRFOU_CompCap(state, CompSpdActual, Tsuction, Tdischarge, h_IU_evap_in, h_comp_in, Q_c_tot, Ncomp);
Real64 Q_h_tot; // Total condenser capacity [W]
Real64 Q_h_TU_PL; // Heating load to be met at heating mode, including the piping loss (W)
Real64 &Q_h_OU, // OU condenser load [W]
Q_h_tot = Q_c_tot + Ncomp;
Q_h_OU = Q_h_tot - Q_h_TU_PL;
Following is the debug print
01/02 07-4 Q_h_OU=-14.889397577117904=285.70383699004094 - 300.59323456715885
For this specific instance, the Q_h_TU_PL
is mostly on the piping loss term.
Q_h_TU_PL = TU_HeatingLoad + Pipe_Q_h;
01/02 07-4 Q_h_TU_PL=300.59323456715885=0.8205014721511905 + 299.77273309500765
Maybe being in HR mode 2 should have ensured Q_c_tot + Ncomp
much larger than Q_h_TU_PL
? (as Q_c_tot
and Ncomp
is the compressor performance at the compressor speed rps1_evap
that meets the cooling load Q_c_TU_PL
). But currently it's not.
about the high piping loss
There's also some strange behavior about the very large piping loss.
Piping loss is calculated here, in the iterations (label230 region), other input arguments stay the same, the h_IU_cond_in
updates, leading to updates in piping loss (Pipe_Q_h
).
this->VRFOU_PipeLossH(
state, m_ref_IU_cond, max(min(Pcond, RefPHigh), RefPLow), h_IU_cond_in, OutdoorDryBulb, Pipe_Q_h, Pipe_DeltP_h, h_comp_out);
The convergence for the label230 checks whether h_comp_out
and h_comp_out_new
is close and whether h_IU_cond_in
is maxed out. So before it's converged h_IU_cond_in
keeps increasing till it reaches the upper bound h_IU_cond_in_up
.
((std::abs(h_comp_out - h_comp_out_new) > Tolerance * h_comp_out) && (h_IU_cond_in < h_IU_cond_in_up))
I've added some debug print after this line.
//* Update h_comp_out in iteration (Label230)
h_comp_out_new = Ncomp / (m_ref_IU_evap + m_ref_OU_evap) + h_comp_in;
The following is the output for the iteration. h_comp_out_new
stays the same while h_comp_out
gets updated in function VRFOU_PipeLossH()
. However, the h_comp_out
is not going in the right direction. It's much larger than h_comp_out_new
at the beginning and keeps increasing each round till h_IU_cond_in
is maxed out. Large h_IU_cond_in
will lead to high piping loss. This potentially contributes to the fact that Q_h_tot - Q_h_TU_PL
is negative (Q_h_TU_PL
gets too large as the piping loss term is large)
-------------before iteration !!! ----------------------------------
01/02 07-4 h_comp_out_new=451462.4133081403=20.990626990893254 / (0.0013282280846405876 + 0) + 435658.9325403223, h_comp_out=25374199.615089763
01/02 07-4 h_comp_out_new=451462.4133081403=20.990626990893254 / (0.0013282280846405876 + 0) + 435658.9325403223, h_comp_out=29927864.42684107
01/02 07-4 h_comp_out_new=451462.4133081403=20.990626990893254 / (0.0013282280846405876 + 0) + 435658.9325403223, h_comp_out=34929581.8246451
01/02 07-4 h_comp_out_new=451462.4133081403=20.990626990893254 / (0.0013282280846405876 + 0) + 435658.9325403223, h_comp_out=40339405.37992493
01/02 07-4 h_comp_out_new=451462.4133081403=20.990626990893254 / (0.0013282280846405878 + 0) + 435658.9325403223, h_comp_out=46137187.431805536
01/02 07-4 h_comp_out_new=451462.4133081403=20.990626990893254 / (0.0013282280846405878 + 0) + 435658.9325403223, h_comp_out=52302549.03700723
01/02 07-4 h_comp_out_new=451462.4133081403=20.990626990893254 / (0.0013282280846405878 + 0) + 435658.9325403223, h_comp_out=58808375.97752049
01/02 07-4 h_comp_out_new=451462.4133081403=20.990626990893254 / (0.0013282280846405878 + 0) + 435658.9325403223, h_comp_out=65654625.1845655
01/02 07-4 h_comp_out_new=451462.4133081403=20.990626990893254 / (0.0013282280846405878 + 0) + 435658.9325403223, h_comp_out=72837775.9464217
01/02 07-4 h_comp_out_new=451462.4133081403=20.990626990893254 / (0.0013282280846405876 + 0) + 435658.9325403223, h_comp_out=80330393.31041604
01/02 07-4 h_comp_out_new=451462.4133081403=20.990626990893254 / (0.0013282280846405878 + 0) + 435658.9325403223, h_comp_out=88762784.65486081
-------------after iteration !!! ----------------------------------
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
So during these iterations h_comp_out_new did not change but h_comp_out did change? That makes no sense. It feels like this iteration loop isn't updating something that SHOULD change in the h_comp_out_new equation otherwise the loop should terminate.
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Yeah, for the specific time step when the fan power became negative, this is what happens. Maybe that could be another criteria (checking whether h_comp_out_new changes) to add to the convergence check
per Mike's comment, #10649 (comment), Q_coil should not be negative, remove the abs(Q_coil) fix Q_evap_req will be negative if Q_cond_req < CompEvaporatingPWRSpd(CounterCompSpdTemp). This leads to negative compressor speed. Temtatively fix it like this. According to comment here #10649 (comment), The h_comp_out and h_comp_out_new could keep getting farther and farther from each other if h_cond_IU_in can only increase in the iteration. Addressing this by adding a direction where h_cond_IU can decrease as well.
Could we change the review process on this model to require a graph that shows how this fix changes the result? This model is so hard to understand that reviewing code is not productive. Let's look at a result and then discuss code. Adding new report variables that show certain data does not go negative might be a good path forward. I would hope that an iteration loop that hits a rail would be easily identified in a graph. |
Good point. I'll produce plots illustrating before vs after the fix how fan power changes |
@rraustad I added a plot comparing the before and after OU fan power difference. |
That plot looks good. And there are no more negative condenser fan power results? I assume no so this should be ready. |
Right, just one time step with negative fan power. |
Hi @dareumnam and @rraustad , some more details are in this comment #10649 (comment). The high-level understanding I have is:
|
So the model has other issues that need to be fixed but we should never let the oa fan power be negative. |
@mjwitte Thanks for your insight. I think we’ll need more time to fix this. I’ll move the milestone to 25.1. |
Thanks @mjwitte and @dareumnam. Even if the current change in convergence criteria fixed the negative fan power, maybe more extensive testing is needed |
This reverts commit 35d4b69.
When Q_cond_req < ComoEvaporatingPWRSpd(1), Q_evap_req will be negative, the calculated compressor speed will be negative. The case where Q_cond_req < ComoEvaporatingPWRSpd(1) need to be considered, where compressor speed is dependent on the compressour power curve output value. CompSpdActual argument VRFOU_CompCap is an int, but the value passed in was originally a real. This casting from int to real will truncate the value. If the value is less than 1, it will be set to 0.
Hi @mjwitte and @rraustad I might have found the culprit for the negative fan power. The negative |
@@ -13726,6 +13726,9 @@ void VRFCondenserEquipment::VRFOU_CompSpd( | |||
|
|||
} else { | |||
CompSpdActual = this->CompressorSpeed(1) * (Q_evap_req * C_cap_operation) / CompEvaporatingCAPSpd(1); | |||
if (Q_cond_req - CompEvaporatingPWRSpd(CounterCompSpdTemp) < 0.0) { // use compressor power to meet condenser required load | |||
CompSpdActual = this->CompressorSpeed(1) * (Q_cond_req * C_cap_operation) / CompEvaporatingPWRSpd(1); | |||
} | |||
} |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
@yujiex I think I understand the intent here. This could be simpler.
} else {
if (Q_evap_req < 0.0) { // use compressor power to meet condenser required load
CompSpdActual = this->CompressorSpeed(1) * (Q_cond_req * C_cap_operation) /CompEvaporatingPWRSpd(1);
} else {
CompSpdActual = this->CompressorSpeed(1) * (Q_evap_req * C_cap_operation) / CompEvaporatingCAPSpd(1);
}
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Indeed, this is more clear.
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
What I don't understand is what looks like a COP term = Qc / PWR. I just don't see how that gets back to a speed 1 fraction. What am I missing?
CompSpdActual = this->CompressorSpeed(1) * (Q_cond_req * C_cap_operation) /CompEvaporatingPWRSpd(1);
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
@rraustad The way I think about this is when Q_cond_req - CompEvaporatingPWRSpd(1) <= 0.0
, then what CompEvaporatingPWRSpd(1)
can supply is too much to meet Q_cond_req
. The speed should be somewhere between 0 and the 1st speed level. So in this case Q_cond_req
should be met by CompEvaporatingPWRSpd(1) * ratio
. This ratio
is calculated as Q_cond_req / CompEvaporatingPWRSpd(1)
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
But CompEvaporatingPWRSpd is power, not capacity. So Q_cond_req / CompEvaporatingPWRSpd(1)
looks strange to me. Shouldn't both equations have CompEvaporatingCAPSpd in the denominator (line 13729)?
Array1D<Real64> CompEvaporatingPWRSpd; // Array for the compressor power at certain speed [W]
Array1D<Real64> CompEvaporatingCAPSpd; // Array for the evaporating capacity at certain speed [W]
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
I can also try to change the VRF evaporative capacity to make it reach higher speed levels.
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Can you make it span speeds? like from speed 1 to speed 3? I want to see what Q_evap_req * C_cap_operating / CompEvaporatingCAPSpd(x) looks like (or your derivation). I suspect there are discontinuities because C_cap_operatiion = 0.6. And make a scatter plot like before. Q_evap_req versus compressor speed.
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Oh I see, your plot is Q_evap_req versus comp speed. I was confused because I didn't see a 45 degree line like I was expecting. Why is Q_evap_req = 2000 at comp speeds 0 - 10000 ??
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Somehow there's some weird thing happening when I plot with excel. CompSpdActual is always below 6000 for both the feature and develop branch output, but it somehow plotted it out to over 10000. I have attached the data here
plot data.zip
I used R to plot, this is how they look
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Unit tests pass, defect file has no negative fan power, but the overall result changes very slightly (annual simulation). This is good once the code is updated as suggested.
Thanks, @mjwitte . I just updated the code according to suggestions here: #10649 (comment) |
Well that's weird...cppcheck couldn't be installed on the action runner? It's always something... :) I'll look into it. |
If you feel like this needs more commits, pulling develop in will get the code integrity check passing. Don't waste CI cycles purely for that though, only if you need more relevant commits here. |
Hi @Myoldmopar, I don't think I have more commits relevant to this bug fix right now. I guess I will not pull develop just to fix the integrity check. |
C_cap_operation was used in the evaporative load adjsutment but not power. not sure if this is intended. Maybe just remove this for now Q_evap_req is no longer used in the calculation, remove it
how r is derived: in the original code Q_evap_req = Q_cond_req - CompEvaporatingPWRSpd(CounterCompSpdTemp); I think the intent was Q_cond_req = Q_req = Q_evap_req + compressor heat but compressor heat might not actually be CompEvaporatingPWRSpd(CounterCompSpdTemp) let k be the speed level C be the short form for C_cap_operation PWR(.) be the short form of CompEvaporatingPWRSpd(.) CAP(.) be the short form of CompEvaporatingCAPSpd(.) spd(.) be the short form of this->CompressorSpeed(.) deltaPWR be PWR(k) - PWR(k - 1) deltaCAP be CAP(k) - CAP(k - 1) I think compressor heat should be this instead of just PWR(k) compressor heat = deltaPWR * r + PWR(k - 1) so Q_cond_req = Q_req = Q_evap_req + deltaPWR * r + PWR(k - 1) <---- eq 1 we also know this from the CompSpdActual calculation equation that CompSpdActual = Spd(k - 1) + deltaSpd / deltaCAP * (Q_evap_req * C - CAP(k - 1)) so we call the following r r = (Q_evap_req * C - CAP(k - 1)) / deltaCAP so CompSpdActual = Spd(k - 1) + deltaSpd * r arranging terms in eq 1 Q_cond_req - deltaPWR * r - PWR(k - 1) = Q_evap_req (Q_cond_req - deltaPWR * r - PWR(k - 1)) * C - CAP(k - 1) = Q_evap_req * C - CAP(k - 1) ((Q_cond_req - deltaPWR * r - PWR(k - 1)) * C - CAP(k - 1)) / deltaCAP = (Q_evap_req * C - CAP(k - 1)) / deltaCAP ((Q_cond_req - deltaPWR * r - PWR(k - 1)) * C - CAP(k - 1)) / deltaCAP = r (Q_cond_req - deltaPWR * r - PWR(k - 1)) * C - CAP(k - 1) = deltaCAP * r (Q_cond_req - PWR(k - 1)) * C - CAP(k - 1) = deltaCAP * r + deltaPWR * r * C so r = ((Q_cond_req - PWR(k - 1)) * C - CAP(k - 1)) / (deltaCAP + deltaPWR * C) = ((Q_cond_req - PWR(k - 1)) - CAP(k - 1)/C) / (deltaCAP/C + deltaPWR) in the special case where k = 1, then k - 1, PWR(k - 1) and CAP(k - 1) will all be 0 r = ((Q_cond_req) * C) / (CAP(1) + PWR(1) * C) = (Q_cond_req) / (CAP(1)/C + PWR(1))
@rraustad I've discussed with colleagues (Kaiyu and Tianzhen) about this This is the documentation Since the performance curve is measured in a test condition, with specific superheating and subcooling degrees, to apply the performance curves of evaporative capacity (they're functions of condensing and evaporating temperatures), we'll also need to consider this difference between testing (or rated) and the real condition in superheating and subcooling. |
OK, that makes sense. What does not make sense is why C_cap_operation = 0.6. Is this compressor operating so far from the rating point that the compressor is providing 60% of it's rated capacity? some Density/Enthalpy tables here. Regardless of this, I think if this model is now behaving better you can move on with getting this merged and worry about this later. |
There might be some complexity in this adjustment factor calculation at low load. I saw one place with a bound to this adjustment factor inside
|
At least the author anticipated this type of range. I think you can move on from here. |
Agree. Thanks for investigating this with me :) |
Pull request overview
CompSpdActual
is casted from real to int in functionVRFOU_CompCap
: theCompSpdActual
(an int) that's fed intoVRFOU_CompCap
gets its value from the output of functionVRFOU_CompSpd
(which is a real). As a result, whenVRFOU_CompCap
gets its inputCompSpdActual
, it will cast it from real to int. When the value is small (less than 1), it will be zeroed out. The PR fixes the problem by changing the type ofCompSpdActual
from int to real.Description of the fix
When running
VariableRefrigerantFlow_FluidTCtrl_HR_5Zone.idf
with Miami airport epw, using detailed timestep, with runperiod from 1/1 to 1/7, there are some negative fan power values like thisTracing the code, we can see these values are calculated in
VRFHR_OU_HR_Mode
and stored inN_fan_OU
The following are related code snippets
The
m_air
calculation is related to the operation mode, which seems problematic.The operation mode is related to the following two
rps
terms (rps1_evap <= rps2_cond
indicates it's in mode 5 of heating dominant mode)When the load is very small,
rps2_cond
could become negative whenQ_cond_req < CompEvaporatingPWRSpd(1)
, as inVRFOU_CompSpd
function else branch (Q_type != HXOpMode::EvapMode
)with this calculation, even when heating load is larger than cooling load, it might still report as cooling dominant
This is a snapshot of how the problematic section of code
Previously I thought a separate edge case need to be handled when
Q_evap_req = Q_cond_req - CompEvaporatingPWRSpd(CounterCompSpdTemp) < 0.0
. However, the compressor heat termCompEvaporatingPWRSpd(CounterCompSpdTemp)
might need to multiply by something. Afterall, when the system is cycling, the compressor heat should also only be a portion, not directly curve value x rated capacity.The following are some derivation about how I think this should be done.
There's a lingering doubt about the multiplier
C_cap_operation
.This is the signature of the function
VRFOU_CapModFactor
.The purpose statement in the function body says
In the function it is computed as
C_cap_operation = C_cap_density * C_cap_enthalpy;
whereIt is usually multiplied to the
Q_evap_req
term (required evaporative capacity).
A quick plot of the
C_cap_operation
distribution inVRFOU_CompSpd
looks like the followingThe following is the relation ship between
Q_evap_req
and theCompSpdActual
before vs after the fix (updated)
The negative fan power is removed after the fix. The following plot shows how the negative fan power changes after the fix (blue is before the fix, orange is after the fix), using Miami and Atlanta weather inputs.
Attached is the simulation output comparison table.
compare_fan_power_dev_feature.xlsx