Skip to content

Commit

Permalink
Merge pull request #116 from Jalle19/alarm-refact2
Browse files Browse the repository at this point in the history
Refactor non-string keyed objects into arrays
  • Loading branch information
Jalle19 authored Aug 16, 2024
2 parents ce918d0 + a2624b1 commit 104c9e7
Show file tree
Hide file tree
Showing 4 changed files with 68 additions and 64 deletions.
101 changes: 54 additions & 47 deletions app/enervent.mjs
Original file line number Diff line number Diff line change
Expand Up @@ -38,54 +38,61 @@ export const AVAILABLE_SETTINGS = {
'defrostingAllowed': 55,
}

export const AVAILABLE_ALARMS = {
// Alarm number
// Name and descr based on Enervent EN EDA Modbus regirsters: 3x0385
// Waste air is used in some places where we don't care about if it's before (Extract)
// or after (Exhaust) the HRC. Filter sits before HRC, and fans after HRC.

1: { name: 'TE5SupplyAirAfterHRCold', description: 'TE5 Supply air after heat recovery cold' },
2: { name: 'TE10SupplyAirAfterHeaterCold', description: 'TE10 Supply air after heater cold' },
3: { name: 'TE10SupplyAirAfterHeaterHot', description: 'TE10 Supply air after heater hot' },
4: { name: 'TE20RoomTempHot', description: 'TE20 Room temperature hot' },
5: { name: 'TE30ExtractAirCold', description: 'TE30 Extract air cold' },
6: { name: 'TE30ExtractAirHot', description: 'TE30 Extract air hot' },
7: { name: 'HPError', description: 'Heatpump' },
8: { name: 'EHError', description: 'Electrical heater' },
9: { name: 'ReturnWaterCold', description: 'Return water cold' },
10: { name: 'HRError', description: 'Heat recovery' },
11: { name: 'CoolingError', description: 'Cooling' },
12: { name: 'EmergencyStop', description: 'Emergency stop' },
13: { name: 'FireRisk', description: 'Fire risk' },
14: { name: 'ServiceReminder', description: 'Service reminder' },
15: { name: 'EHPDA', description: 'Electrical heater pressure switch' },
16: { name: 'SupplyFilterDirty', description: 'Supply filter dirty' },
17: { name: 'ExtractFilterDirty', description: 'Waste filter dirty' },
20: { name: 'SupplyFanPressureError', description: 'Supply fan pressure' },
21: { name: 'ExtractFanPressureError', description: 'Waste fan pressure' },
}
export const AVAILABLE_ALARMS = [
{ name: 'TE5SupplyAirAfterHRCold', description: 'TE5 Supply air after heat recovery cold', type: 1 },
{ name: 'TE10SupplyAirAfterHeaterCold', description: 'TE10 Supply air after heater cold', type: 2 },
{ name: 'TE10SupplyAirAfterHeaterHot', description: 'TE10 Supply air after heater hot', type: 3 },
{ name: 'TE20RoomTempHot', description: 'TE20 Room temperature hot', type: 4 },
{ name: 'TE30ExtractAirCold', description: 'TE30 Extract air cold', type: 5 },
{ name: 'TE30ExtractAirHot', description: 'TE30 Extract air hot', type: 6 },
{ name: 'HPError', description: 'Heatpump', type: 7 },
{ name: 'EHError', description: 'Electrical heater', type: 8 },
{ name: 'ReturnWaterCold', description: 'Return water cold', type: 9 },
{ name: 'HRError', description: 'Heat recovery', type: 10 },
{ name: 'CoolingError', description: 'Cooling', type: 11 },
{ name: 'EmergencyStop', description: 'Emergency stop', type: 12 },
{ name: 'FireRisk', description: 'Fire risk', type: 13 },
{ name: 'ServiceReminder', description: 'Service reminder', type: 14 },
{ name: 'EHPDA', description: 'Electrical heater pressure switch', type: 15 },
{ name: 'SupplyFilterDirty', description: 'Supply filter dirty', type: 16 },
{ name: 'ExtractFilterDirty', description: 'Waste filter dirty', type: 17 },
{ name: 'SupplyFanPressureError', description: 'Supply fan pressure', type: 20 },
{ name: 'ExtractFanPressureError', description: 'Waste fan pressure', type: 21 },
]

export const SENSOR_TYPE_NONE = 'NONE'
export const SENSOR_TYPE_CO2 = 'CO2'
export const SENSOR_TYPE_RH = 'RH'
export const SENSOR_TYPE_ROOM_TEMP = 'ROOM_TEMP'

// 0=NA, 1=CO2_1, 2=CO2_2, 3=CO2_3, 4=RH_1, 5=RH_2, 6=RH_3, 7=OUT_TERM, 8=ROOM_TERM_1,
// 9=ROOM_TERM_2, 10=ROOM_TERM_3, 11=TEMP_SP, 12=Time relay, 13=External heating disable, 14=External cooling disable,
// 15=PDE10, 16=PDE30
export const ANALOG_INPUT_SENSOR_TYPES = {
export const ANALOG_INPUT_SENSOR_TYPES = [
// Skip sensor types we can't handle
0: { type: SENSOR_TYPE_NONE },
1: { type: SENSOR_TYPE_CO2, name: 'analogInputCo21', description: 'CO2 #1' },
2: { type: SENSOR_TYPE_CO2, name: 'analogInputCo22', description: 'CO2 #1' },
3: { type: SENSOR_TYPE_CO2, name: 'analogInputCo23', description: 'CO2 #1' },
4: { type: SENSOR_TYPE_RH, name: 'analogInputHumidity1', description: 'RH #1' },
5: { type: SENSOR_TYPE_RH, name: 'analogInputHumidity2', description: 'RH #1' },
6: { type: SENSOR_TYPE_RH, name: 'analogInputHumidity3', description: 'RH #1' },
8: { type: SENSOR_TYPE_ROOM_TEMP, name: 'analogInputRoomTemperature1', description: 'Room temperature #1' },
9: { type: SENSOR_TYPE_ROOM_TEMP, name: 'analogInputRoomTemperature2', description: 'Room temperature #1' },
10: { type: SENSOR_TYPE_ROOM_TEMP, name: 'analogInputRoomTemperature3', description: 'Room temperature #1' },
}
{ type: 0, sensorType: SENSOR_TYPE_NONE },
{ type: 1, sensorType: SENSOR_TYPE_CO2, name: 'analogInputCo21', description: 'CO2 #1' },
{ type: 2, sensorType: SENSOR_TYPE_CO2, name: 'analogInputCo22', description: 'CO2 #1' },
{ type: 3, sensorType: SENSOR_TYPE_CO2, name: 'analogInputCo23', description: 'CO2 #1' },
{ type: 4, sensorType: SENSOR_TYPE_RH, name: 'analogInputHumidity1', description: 'RH #1' },
{ type: 5, sensorType: SENSOR_TYPE_RH, name: 'analogInputHumidity2', description: 'RH #1' },
{ type: 6, sensorType: SENSOR_TYPE_RH, name: 'analogInputHumidity3', description: 'RH #1' },
{
type: 8,
sensorType: SENSOR_TYPE_ROOM_TEMP,
name: 'analogInputRoomTemperature1',
description: 'Room temperature #1',
},
{
type: 9,
sensorType: SENSOR_TYPE_ROOM_TEMP,
name: 'analogInputRoomTemperature2',
description: 'Room temperature #1',
},
{
type: 10,
sensorType: SENSOR_TYPE_ROOM_TEMP,
name: 'analogInputRoomTemperature3',
description: 'Room temperature #1',
},
]

export const AUTOMATION_TYPE_LEGACY_EDA = 'LEGACY_EDA'
export const AUTOMATION_TYPE_EDA = 'EDA'
Expand Down Expand Up @@ -201,9 +208,9 @@ export const parseStateBitField = (state) => {

export const hasRoomTemperatureSensor = (sensorTypesResult) => {
for (let i = 0; i < 6; i++) {
const sensorType = ANALOG_INPUT_SENSOR_TYPES[sensorTypesResult.data[i]]
const sensor = ANALOG_INPUT_SENSOR_TYPES.find((sensor) => sensor.type === sensorTypesResult.data[i])

if (sensorType.type === SENSOR_TYPE_ROOM_TEMP) {
if (sensor?.sensorType === SENSOR_TYPE_ROOM_TEMP) {
return true
}
}
Expand All @@ -215,17 +222,17 @@ export const parseAnalogSensors = (sensorTypesResult, sensorValuesResult) => {
const sensorReadings = {}

for (let i = 0; i < 6; i++) {
const sensorType = ANALOG_INPUT_SENSOR_TYPES[sensorTypesResult.data[i]]
const sensor = ANALOG_INPUT_SENSOR_TYPES.find((sensor) => sensor.type === sensorTypesResult.data[i])

switch (sensorType.type) {
switch (sensor?.sensorType) {
// Use raw value
case SENSOR_TYPE_CO2:
case SENSOR_TYPE_RH:
sensorReadings[sensorType.name] = sensorValuesResult.data[i]
sensorReadings[sensor.name] = sensorValuesResult.data[i]
break
// Parse as temperature
case SENSOR_TYPE_ROOM_TEMP:
sensorReadings[sensorType.name] = parseTemperature(sensorValuesResult.data[i])
sensorReadings[sensor.name] = parseTemperature(sensorValuesResult.data[i])
break
}
}
Expand Down
2 changes: 1 addition & 1 deletion app/homeassistant.mjs
Original file line number Diff line number Diff line change
Expand Up @@ -303,7 +303,7 @@ export const configureMqttDiscovery = async (modbusClient, mqttClient) => {
// Binary sensors for alarms
let binarySensorConfigurationMap = {}

for (const [, alarm] of Object.entries(AVAILABLE_ALARMS)) {
for (const alarm of AVAILABLE_ALARMS) {
binarySensorConfigurationMap[alarm.name] = createAlarmConfiguration(configurationBase, alarm)
}

Expand Down
22 changes: 10 additions & 12 deletions app/modbus.mjs
Original file line number Diff line number Diff line change
Expand Up @@ -339,17 +339,15 @@ export const getDeviceInformation = async (modbusClient) => {
}

export const getAlarmSummary = async (modbusClient) => {
let alarmSummary = { ...AVAILABLE_ALARMS }
const alarmSummary = []
const newestAlarm = await getNewestAlarm(modbusClient)

for (const type in alarmSummary) {
// Use "off" as the default alarm state, most likely to be true
alarmSummary[type].state = 0

// Use the state from the newest alarm
if (type === newestAlarm.type) {
alarmSummary[type].state = newestAlarm.state
}
for (const alarm of AVAILABLE_ALARMS) {
// Add each available alarm and have the state reflect the currently active alarm's state, if any
alarmSummary.push({
...alarm,
state: alarm.type === newestAlarm?.type ? newestAlarm?.state : 0,
})
}

return alarmSummary
Expand All @@ -362,13 +360,13 @@ export const getNewestAlarm = async (modbusClient) => {
const state = result.data[1]
const timestamp = parseAlarmTimestamp(result)

if (AVAILABLE_ALARMS[type] === undefined) {
const alarm = AVAILABLE_ALARMS.find((alarm) => alarm.type === type)
if (alarm === undefined) {
return null
}

return {
...AVAILABLE_ALARMS[type],
type,
...alarm,
state,
timestamp,
}
Expand Down
7 changes: 3 additions & 4 deletions tests/enervent.test.mjs
Original file line number Diff line number Diff line change
Expand Up @@ -181,14 +181,13 @@ test('parseAnalogSensors', () => {
'analogInputCo21': 450,
})

// Multitude of sensors
typesResult = { data: [1, 2, 4, 5, 8, 9] }
valuesResult = { data: [450, 481, 45, 46, 192, 201] }
// Multitude of sensors, including ones we don't support
typesResult = { data: [1, 2, 4, 7, 8, 9] }
valuesResult = { data: [450, 481, 45, 210, 192, 201] }
expect(parseAnalogSensors(typesResult, valuesResult)).toEqual({
'analogInputCo21': 450,
'analogInputCo22': 481,
'analogInputHumidity1': 45,
'analogInputHumidity2': 46,
'analogInputRoomTemperature1': 19.2,
'analogInputRoomTemperature2': 20.1,
})
Expand Down

0 comments on commit 104c9e7