You signed in with another tab or window. Reload to refresh your session.You signed out in another tab or window. Reload to refresh your session.You switched accounts on another tab or window. Reload to refresh your session.Dismiss alert
ESP32 on Arduino codebase via PlatformIO. With a MAX13487e.
Scenario:
Reading a three phase network analyzer, slave device 1, baud 9600.
Steps to Reproduce:
A raw serial message read/wrtie does produce the right message and response from the device. Somehow when using the ModbusMaster library I keep getting an Error 227.
void sendModbusRequest() {
uint8_t request[] = {0x01, 0x03, 0x01, 0x66, 0x00, 0x02}; // Device 1, Function 3
uint16_t crc = calculateCRC(request, sizeof(request));
// Append CRC to request
uint8_t crcLow = crc & 0xFF;
uint8_t crcHigh = (crc >> 8) & 0xFF;
Serial2.write(request, sizeof(request));
Serial2.write(crcLow);
Serial2.write(crcHigh);
}
//Serial2.begin(9600, SERIAL_8N1, BOARD_485_RX, BOARD_485_TX);
void readModbusResponse() {
int availableBytes = Serial2.available();
if (availableBytes > 0) {
Serial.print("Response: ");
while (availableBytes--) {
int byteReceived = Serial2.read();
if (byteReceived == -1) break; // Just in case
// Print each byte in HEX format
if (byteReceived < 16) {
Serial.print("0"); // Print leading zero for single digit hex values
}
Serial.print(byteReceived, HEX);
Serial.print(" "); // Add space between bytes for readability
}
Serial.println(); // Newline after the complete message
} else {
Serial.println("No response");
}
}
Current not-working code for ModbusMaster:
void connectmodbus(){
Serial2.begin(9600, SERIAL_8N1, BOARD_485_RX, BOARD_485_TX);
node.begin(1, Serial2);
pinMode(GPIO_PUSE, OUTPUT);
tick.attach_ms(1000, []() {
digitalWrite(GPIO_PUSE, 1 - digitalRead(GPIO_PUSE));
});
pinMode(BOARD_POWER_ON, OUTPUT);
digitalWrite(BOARD_POWER_ON, HIGH);
pinMode(BOARD_485_EN, OUTPUT);
digitalWrite(BOARD_485_EN, LOW);
}
void loop(){
static uint32_t i;
uint8_t j, result;
i++;
// set word 0 of TX buffer to least-significant word of counter (bits 15..0)
//node.setTransmitBuffer(0, lowWord(i));
// set word 1 of TX buffer to most-significant word of counter (bits 31..16)
//node.setTransmitBuffer(1, highWord(i));
node.clearResponseBuffer();
result = node.readHoldingRegisters(0x0166,2);
//readModbusResponse();
if (result == node.ku8MBSuccess) {
Serial.println("Request successful");
// If successful, read the data
for (uint8_t i = 0; i < 2; i++) { // Assuming 2 registers were requested
uint16_t data = node.getResponseBuffer(i);
Serial.print("Register ");
Serial.print(i);
Serial.print(": ");
Serial.println(data, HEX);
}
} else {
Serial.print("Request failed with error code: ");
Serial.println(result);
}
//sendModbusRequest();
delay(1000); // Wait a bit for the response
}
Expected Result:
Response value from device >> 3C A6 43 6A
Actual Result:
Error 227.
The text was updated successfully, but these errors were encountered:
ModbusMaster version
4-20ma/ModbusMaster@^2.0.1
Arduino IDE version
Visual Studio Code - PlatformIO
Arduino Hardware
ESP32 on Arduino codebase via PlatformIO. With a MAX13487e.
Scenario:
Reading a three phase network analyzer, slave device 1, baud 9600.
Steps to Reproduce:
A raw serial message read/wrtie does produce the right message and response from the device. Somehow when using the ModbusMaster library I keep getting an Error 227.
Response with code below: 01 03 01 66 00 02 25 E8 01 03 04 3C A6 43 6A A7 5F;
Current not-working code for ModbusMaster:
Expected Result:
Response value from device >> 3C A6 43 6A
Actual Result:
Error 227.
The text was updated successfully, but these errors were encountered: